zwave-js/.config-db/devices/0x019b/z-temp3.json

243 lines
5 KiB
JSON
Raw Permalink Normal View History

2025-01-10 22:05:04 -08:00
{
"manufacturer": "Heatit",
"manufacturerId": "0x019b",
"label": "Z-TEMP3",
"description": "Thermostat",
"devices": [
{
"productType": "0x0031",
"productId": "0x3101",
"zwaveAllianceId": 4908
}
],
"firmwareVersion": {
"min": "0.0",
"max": "255.255"
},
"associations": {
"1": {
"label": "Lifeline",
"maxNodes": 1,
"isLifeline": true
},
"2": {
"label": "Binary Switch Set",
"maxNodes": 10
},
"3": {
"label": "Thermostat Setpoint Set",
"maxNodes": 10
},
"4": {
"label": "Thermostat Mode Set",
"maxNodes": 10
}
},
"paramInformation": [
{
"#": "1",
"$import": "~/templates/master_template.json#base_enable_disable_inverted",
"label": "Local Control",
"defaultValue": 0
},
{
"#": "2",
"label": "Min Temp Limit",
"valueSize": 2,
"unit": "0.1 °C",
"minValue": 50,
"maxValue": 400,
"defaultValue": 50
},
{
"#": "3",
"label": "Max Temp Limit",
"valueSize": 2,
"unit": "0.1 °C",
"minValue": 50,
"maxValue": 400,
"defaultValue": 400
},
{
"#": "4",
"label": "Temp Sensor Calibration",
"valueSize": 1,
"unit": "0.1 °C",
"minValue": -60,
"maxValue": 60,
"defaultValue": 0,
"unsigned": false
},
{
"#": "5",
"label": "Regulation Mode",
"valueSize": 1,
"defaultValue": 0,
"allowManualEntry": false,
"options": [
{
"label": "Hysteresis",
"value": 0
},
{
"label": "PWM",
"value": 1
}
]
},
{
"#": "6",
"label": "Update Interval",
"description": "Allowable range: 0, 150-2000",
"valueSize": 2,
"unit": "seconds",
"minValue": 0,
"maxValue": 65535,
"defaultValue": 3600,
"unsigned": true,
"options": [
{
"label": "Only on change",
"value": 0
}
]
},
{
"#": "7",
"label": "Temperature Control Hysteresis",
"valueSize": 1,
"unit": "0.1 °C",
"minValue": 3,
"maxValue": 30,
"defaultValue": 5
},
{
"#": "8",
"label": "Temperature Display",
"valueSize": 1,
"defaultValue": 0,
"allowManualEntry": false,
"options": [
{
"label": "Setpoint",
"value": 0
},
{
"label": "Measured",
"value": 1
}
]
},
{
"#": "9",
"label": "Active Display Brightness",
"valueSize": 1,
"unit": "10 %",
"minValue": 1,
"maxValue": 10,
"defaultValue": 10
},
{
"#": "10",
"label": "Temperature Report Interval",
"valueSize": 2,
"unit": "seconds",
"minValue": 150,
"maxValue": 65535,
"defaultValue": 990,
"unsigned": true
},
{
"#": "11",
"label": "Temperature Report Hysteresis",
"valueSize": 1,
"unit": "0.1 °C",
"minValue": 1,
"maxValue": 100,
"defaultValue": 10
},
{
"#": "12",
"label": "Humidity Report Interval",
"valueSize": 2,
"unit": "seconds",
"minValue": 150,
"maxValue": 65535,
"defaultValue": 990,
"unsigned": true
},
{
"#": "13",
"label": "Humidity Report Hysteresis",
"valueSize": 1,
"unit": "%",
"minValue": 1,
"maxValue": 100,
"defaultValue": 25
},
{
"#": "14",
"label": "Heating Setpoint",
"valueSize": 2,
"unit": "0.1 °C",
"minValue": 50,
"maxValue": 400,
"defaultValue": 210
},
{
"#": "15",
"label": "Cooling Setpoint",
"valueSize": 2,
"unit": "0.1 °C",
"minValue": 50,
"maxValue": 400,
"defaultValue": 250
},
{
"#": "16",
"label": "Eco Setpoint",
"valueSize": 2,
"unit": "0.1 °C",
"minValue": 50,
"maxValue": 400,
"defaultValue": 180
},
{
"#": "17",
"label": "Operating Mode",
"valueSize": 1,
"defaultValue": 1,
"allowManualEntry": false,
"options": [
{
"label": "Off",
"value": 0
},
{
"label": "Heating",
"value": 1
},
{
"label": "Cooling",
"value": 2
},
{
"label": "Eco",
"value": 3
}
]
},
{
"#": "18",
"$import": "~/templates/master_template.json#base_enable_disable",
"label": "Open Window Detection"
}
],
"metadata": {
"inclusion": "Hold the Center button for 5 seconds. The display will show “OFF”\n Press the ”+” button once to see “CON” in the display.\n Start the add/remove device process in your primary controller.\n Start the configuration mode on the thermostat by holding the Center button for approximately 2 seconds.",
"exclusion": "Hold the Center button for 5 seconds. The display will show “OFF”\n Press the ”+” button once to see “CON” in the display.\n Start the add/remove device process in your primary controller.\n Start the configuration mode on the thermostat by holding the Center button for approximately 2 seconds.",
"reset": "Enter the menu by holding the Center button for about 5seconds, navigate in the menu with the ”+” button til you see FACT. Press the Center button until you see “-- --” blinking in the display, then hold for about 5 seconds to perform a reset. You may also initiate a reset by holding the Right and Center buttons for 55 seconds.",
"manual": "https://media.heatit.com/3872"
}
}